REM Live
The purpose of the REM live range Electrical Safety
Products is to provide a WARNING OF THE PRESENCE OF ELECTRICITY.
The person performing the work in the isolator or control panel cannot
fail to see the flashes immediately upon opening the enclosure door and
therefore receives the warning that the equipment still has a
potentially lethal condition.
RL-4
The RL-4 is designed to fit inside a control panel or switch and
mounts on standard DIN rail.
The RL-4 consists of a polycarbonate enclosure, which contains a series
of LED's and a legend displaying the following conditions.
Phase and Neutral indication
Indication of any voltage present between 24v - 700vac and 24v - 1000vdc
A safety message with instructions
The RL-4 contains electronic circuits which connect via terminals and
user wiring to a point as close as possible to the point of the
electrical supply to be monitored - usually immediately after the
disconnect switch. |
|
 |
The concept of operation is that when the power is present, then the
LED displays in the RL-4 would be illuminated with some intense,
flashing LED's that attract attention. These LED's remain operational
until all voltage has decayed to less than 24v on all connections.
The legend on RL-4 advises this person to employ other safety
procedures and test further before touching.
Another function of RL-4 is to give a continuous reminder to
personnel when working on or near live equipment, for test and
maintenance purposes, that the situation is one that needs additional
care due to the presence of potentially lethal voltage.
Mini Remlive MRL-1
The MRL-1 is designed to fit inside a control panel or
switch and mounts on standard DIN rail.
The MRL-1 consists of a polycarbonate enclosure, which contains
a series of LED's and a legend displaying the following
conditions for single phase circuits.
Phase and Neutral indication
Indication of any voltage present between 24v and 420v ac / 24v
and 600v dc
A safety message with instructions
The MRL-1 contains electronic circuits which connect via
terminals and user wiring to a point as close as possible to the
point of the electrical supply to be monitored - usually
immediately after the disconnect switch or on terminal rails
where voltages come into one control panel, but are fed from
another. |
|
 |
Micro Remlive uRL-1
The Micro is designed to fit through the front of a control
panel or switch and occupies a standard 30mm pushbutton hole. It
is rated at IP 65 for Europe and NEMA 4X for USA
The front face of the Micro consists of a clear polycarbonate
material, behind which are a series of LED’s and a legend
displaying the following conditions :-
Phase and Neutral indication
Indication of any voltage present between 24v and 750v ac / 24v
and 1000v dc - including neutral voltage if present |
|
 |
A safety message with instructions
The Micro contains fully encapsulated, triple redundant, electronic
circuits and the connection is via a flying lead which connects to the
electrical supply as close as possible to the Isolation point - i.e.
immediately after the disconnect switch.
The concept of operation is that when the power supply is in the "ON"
state then the LED displays on the face of the micro would be
illuminated with some flashing LED's to attract attention. These LED's
would remain operational until all voltage has decayed to less than 24v
on all connections including the Neutral.
So the person performing the isolation can see that the Micro is
functional with the power on and see a positive change of state after
correct isolation, because Micro-Remlive will continue to give some form
of illumination until all voltage connected to it is below 24 volts |